SAFETY TESTER
THE SAFETY TESTER IS THE GENERIC TERM TO COVER THE 3 OR 4 TESTS OF THE ELECTRICAL SAFETY STANDARDS, FROM THE INTERNATIONAL STANDARDS

ground bond test (also called bonding test, ground continuity test )
- insulation test (also called high resistance test, megger test)
- hipot test to make a high voltage test (also called dielectric strength test, hipot test, hi-pot test, breakdown test or flash test)
- leakage current measurement (also called line leakage test)
The final purpose of those tests is to validate that the product under test is safe for the end user, and complies with the quality requirements from the Low Voltage Directive (LVD), applicable to the corresponding standards (IEC335, IEC950, IEC601, IEC1010, IEC598, IEC990, IEC204...)
Safety tester selector guide
Sefelec safety tester range
|
Ground continuity/ Ground bond test |
|
Insulation / High resistance test
|
Leakage current / Line leakage test |
Power measurement P,U,I, cosΦ |
Interface |
Software |
|
5-32A AC
40A option
1mΩ - 1,5Ω
|
0-5 kV AC 10mA
|
50 kΩ-200 GΩ / 500V DC
2 TΩ option
1000V DC option
|
FXS501 |
FXS501 |
RS232 included, GPIB, PLC, Ethernet in option |
WINPASS-MX |
|
5-32A AC
40A option
1mΩ - 1,5Ω
|
0-5 kVAC 10mA
0-6 kVDC 4mA
|
50 kΩ-200 GΩ / 500V DC
2 TΩ option
1000V DC option
|
FXS501 |
FXS501 |
RS232 included, GPIB, PLC, Ethernet in option |
WINPASS-MX |
|
5-32A AC
40A option
1mΩ - 1,5Ω |
0-5 kV AC 110mA
|
50 kΩ-200 GΩ / 500V DC
2 TΩ option
1000V DC option
|
FXS501 |
FXS501 |
RS232 included, GPIB, PLC, Ethernet in option |
WINPASS-MX |
|
5-32A AC
40A option
1mΩ - 1,5Ω |
0-5 kVAC 110mA
0-6 kVDC 50mA
|
50 kΩ-200 GΩ / 500V DC
2 TΩ option
1000V DC option
|
FXS501 |
FXS501 |
RS232 included, GPIB, PLC, Ethernet in option |
WINPASS-MX |
|
5-32A AC
40A option
10mΩ - 1,5Ω |
100VDC-10kVDC
1000µA
|
1000kΩ-20GΩ 500VDC to
1500VDC
|
- |
- |
RS232 included, GPIB, PLC, Ethernet in option |
WINPASS-MX |
CXS40 Ground bond tester
 |
5-40A AC
50A option
1
mΩ - 1,5Ω |
|
2,5% |
- |
- |
RS232 included, GPIB, PLC, Ethernet in option |
WINPASS-MX |
|
- |
5 kVAC 110mA max
4 kVDC 40mA max
|
1kV DC
200 GΩ max
|
- |
- |
RS232, dry contacts, USB (option) |
WINPASS-MX |
|
40A AC & DC max |
-
|
-
|
- |
- |
RS232, dry contacts, USB (option) |
WINPASS-MX |
|
40A AC & DC max |
5 kVAC 110mA max
4 kVDC 40mA max
|
1kV DC
200 GΩ max
|
- |
- |
RS232, dry contacts, USB (option) |
WINPASS-MX |
|
|
5 kVAC 40 mA
6 kV DC 10mA |
up to 9.5 GΩ 1000 V DC
|
- |
- |
RS232, USB, signal I/O included |
No |
|
200 mA, 4A,
10A, 25A,
12V AC
0.01Ω to 999Ω
|
0-5kV AC 500VA
0-6kV DC <60VA
|
250V DC
500V DC, 1000V DC
0.01MΩ to 199.9MΩ
|
EN60335-1 EN60950
EN61010
EN60598 |
16A single phase max.
|
RS232, USB, Bluetooth |
Yes
MES Manager
|
Line leakage tester
FXS501(slave) single or three phases

|
XS Series |
XS Series |
XS Series |
IEC335, IEC950, IEC598, IEC601, IEC1010, IEC990
|
Up to 63 A single phase or three phases |
RS232 included, GPIB, PLC, Ethernet in option |
WINPASS-MX |
APPLICATION
MANUFACTURER, LABORATORY, HIGH SPEED PRODUCTION, MAINTENANCE, IN ORDER TO COMPLY WITH THE LOW VOLTAGE DIRECTIVE

• IEC 335 household manufacturer (washing machines, coffee machines, fridges, heaters, boilers, …)
• IEC 204 industrial equipment (compressor, electrical tools, …)
• IEC 598 lighting industry (street lights, professional lighting, medical lighting, bulbs, …)
• IEC 601 medical industry (scanners, surgery equipments, X-ray, electrical beds, …)
• IEC 950 information technology industry (modems, satellite receivers, servers, printers,
cash dispensers, …)
• IEC 1010 measurement, control and laboratories industry (electrical meters, test & measurement equipment, …)
SPECIFICATION OVERVIEW
FROM LABORATORY TO PRODUCTION TESTING,
OUR RANGE COVERS THE FOLLOWING SPECIFICATIONS
• ground bond test up to 40A AC with resistance measurement up to 1,5Ω
• insulation test with DC Voltage from 1V up to 1000 VDC (1V steps)
• hipot test with our ”delta I” exclusive detection type for non destructive testing, up to 5 kVAC,
6 kVDC
• possible destructive hipot test (for investigation and laboratory use) but also hipot test at operating temperature
• leakage current measurement in single or three phases, according to all current international standards
• power measurement and cos φ measurement
• GPIB, RS232, Ethernet, 0-10V, PLC available
• WINPASS-MX software for quality purposes, traceability and professional reporting
Click here to download the above information in pdf format
Cable testing combined with electrical safety testing and measuring instruments is our added value. As a producer of those 3 product families, Sefelec is the unique, worldwide, to have this cable tester global solution. |